Schneider LC1D12CC7C

Main Information

 

Product Series

 
TeSys Deca
 

Product Series

 
TeSys Deca
 

Product Type

 
Contactor
 

Product Short Name

 
LC1D
 

Application Fields of Contactor

 
Applied to AC loads with a power factor greater than or equal to 0.95. Applied to non - inductive or slightly inductive loads, resistance furnaces.
 

Usage Categories

 
AC - 4 AC - 1 AC - 3 AC - 3e
 

Number of Poles

 
3P
 

Rated Working Voltage [Ue]

 
Power circuit: <= 690 V AC, 25...400 Hz Power circuit: <= 300 V DC
 

Rated Working Current [Ie]

 
25 A (when the operating temperature <= 60 °C) when the operating voltage <= 440 V AC, AC - 1 for the power circuit. 12 A (when the operating temperature <= 60 °C) when the operating voltage <= 440 V AC, AC - 3 for the power circuit. 12 A (when the operating temperature <= 60 °C) when the operating voltage <= 440 V AC, AC - 3e for the power circuit.
 

Control Circuit Voltage [Uc]

 
36 V AC, 50/60 Hz
 

Supplementary Information

 

Motor Power (kW)

 
7.5 kW when the operating voltage <= 500 V AC, 50/60 Hz (AC - 3) 3 kW when the operating voltage <= 220/240 V AC, 50/60 Hz (AC - 3) 5.5 kW when the operating voltage <= 380/400 V AC, 50/60 Hz (AC - 3) 5.5 kW when the operating voltage <= 415/440 V AC, 50/60 Hz (AC - 3) 7.5 kW when the operating voltage <= 660/690 V AC, 50/60 Hz (AC - 3) 7.5 kW when the operating voltage <= 500 V AC, 50/60 Hz (AC - 3e) 3 kW when the operating voltage <= 220/240 V AC, 50/60 Hz (AC - 3e) 5.5 kW when the operating voltage <= 380/400 V AC, 50/60 Hz (AC - 3e) 5.5 kW when the operating voltage <= 415/440 V AC, 50/60 Hz (AC - 3e) 7.5 kW when the operating voltage <= 660/690 V AC, 50/60 Hz (AC - 3e)
 

Model

 
LC1D
 

Type of Circuit Contacts

 
3 NO
 

Protective Cover

 
With protective cover
 

Conventional Heating Current [Ith]

 
25 A (when the operating temperature <= 60 °C) for the power circuit. 10 A (when the operating temperature <= 60 °C) for the signal circuit.
 

Rated Short - time Withstand Current [Icw]

 
105 A when the operating temperature <= 40 °C, sustainable for 10 s for the power circuit. 210 A when the operating temperature <= 40 °C, sustainable for 1 s for the power circuit. 30 A when the operating temperature <= 40 °C, sustainable for 10 minutes for the power circuit. 61 A when the operating temperature <= 40 °C, sustainable for 1 minute for the power circuit. 100 A, sustainable for 1 s for the signal circuit. 120 A, sustainable for 500 ms for the signal circuit. 140 A, sustainable for 100 ms for the signal circuit.
 

Fuses Used in Conjunction with Relays

 
10 A gG, for the signal circuit, in accordance with IEC 60947 - 5 - 1. 40 A gG when the operating voltage <= 690 V, in conjunction with Type 1, for the power circuit. 25 A gG when the operating voltage <= 690 V, in conjunction with Type 2, for the power circuit.
 

Average Impedance

 
2.5 mΩ - Ith 25 A, 50 Hz for the power circuit.
 

Rated Insulation Voltage [Ui]

 
Power circuit: 690 V, in accordance with IEC 60947 - 4 - 1. Signal circuit: 690 V, in accordance with IEC 60947 - 1.
 

Overvoltage Category

 
III
 

Pollution Degree

 
3
 

Rated Impulse Withstand Voltage [Uimp]

 
6 kV, in accordance with IEC 60947.
 

Safety and Reliability Level

 
B10d = 1369863 times for contactors with nominal load, in accordance with EN/ISO 13849 - 1. B10d = 20000000 times for contactors with mechanical load, in accordance with EN/ISO 13849 - 1.
 

Mechanical Life

 
15 Mcycles
 

Electrical Life

 
2 Mcycles at 12 A, AC - 3, Ue conditions <= 440 V. 0.8 Mcycles at 25 A, AC - 1, Ue conditions <= 440 V. 2.2 Mcycles at 9 A, AC - 3, Ue conditions 660/690 V. 2 Mcycles at 12 A, AC - 3e, Ue conditions <= 440 V. 2.2 Mcycles at 9 A, AC - 3e, Ue conditions 660/690 V.
 

Control Circuit Characteristics

 
AC at 50/60 Hz
 

Surge Suppression Module

 
No built - in surge suppression module.
 

Control Voltage Limit

 
0.3...0.6 Uc (- 40…60 °C): Coil release, 50/60 Hz. 0.8...1.1 Uc (- 40…60 °C): Coil start, 50 Hz. 0.85...1.1 Uc (- 40…60 °C): Coil start, 60 Hz.
 

Power Consumption (VA) (~50Hz Starting)

 
70 VA at 60 Hz, cos phi 0.75 (at 20 °C) 70 VA at 50 Hz, cos phi 0.75 (at 20 °C)
 

Power Consumption (VA) (~50Hz Holding)

 
5 VA at 60 Hz, cos phi 0.3 (at 20 °C) 6 VA at 50 Hz, cos phi 0.3 (at 20 °C)
 

Heat Dissipation

 
1.5…2.5 W at 50/60 Hz
 

Action Time

 
12...22 ms for closing 4...19 ms for opening
 

Maximum Operating Frequency

 
3600 times/hour at 60 °C
 

Wiring Capacity

 
Power circuit: Bolted fastening 1, 1…4 mm², terminal lug outer diameter Ø: 8 mm, cable type: flexible wire without terminal. Power circuit: Bolted fastening 2, 1…4 mm², terminal lug outer diameter Ø: 8 mm, cable type: flexible wire without terminal. Power circuit: Bolted fastening 1, 1…4 mm², terminal lug outer diameter Ø: 8 mm, cable type: flexible wire with terminal. Power circuit: Bolted fastening 2, 1…2.5 mm², terminal lug outer diameter Ø: 8 mm, cable type: flexible wire with terminal. Power circuit: Bolted fastening 1, 1…4 mm², terminal lug outer diameter Ø: 8 mm, cable type: rigid wire without terminal. Power circuit: Bolted fastening 2, 1…4 mm², terminal lug outer diameter Ø: 8 mm, cable type: rigid wire without terminal. Control circuit: Bolted fastening 1, 1…4 mm², cable type: flexible wire without terminal. Control circuit: Bolted fastening 2, 1…4 mm², cable type: flexible wire without terminal. Control circuit: Bolted fastening 1, 1…4 mm², cable type: flexible wire with terminal. Control circuit: Bolted fastening 2, 1…2.5 mm², cable type: flexible wire with terminal. Control circuit: Bolted fastening 1, 1…4 mm², cable type: rigid wire without terminal. Control circuit: Bolted fastening 2, 1…4 mm², cable type: rigid wire without terminal.
 

Tightening Torque

 
Power circuit: 1.7 N.m through bolted fastening with a flat - bladed screwdriver Ø 6. Power circuit: 1.7 N.m through bolted fastening with a cross - head screwdriver No 2. Control circuit: 1.7 N.m through bolted fastening with a flat - bladed screwdriver Ø 6. Control circuit: 1.7 N.m through bolted fastening with a cross - head screwdriver No 2. Power circuit: 1.7 N.m through cable connector with a flat - bladed screwdriver Ø 6, screw: M3.5. Power circuit: 1.7 N.m through cable connector with a cross - head screwdriver No 2, screw: M3.5. Control circuit: 1.7 N.m through bolted fastening with a pozidriv screwdriver No 2. Power circuit: 1.7 N.m through bolted fastening with a pozidriv screwdriver No 2.
 

Type of Auxiliary Contacts

 
Type Mechanically Connected 1 NO + 1 NC, in accordance with IEC 60947 - 5 - 1. Type Mirror - imaged with the Main Contact State 1 NC, in accordance with IEC 60947 - 4 - 1.
 

Available Auxiliary Contacts per Contactor

 
1 NO + 1 NC
 

Signal Circuit Frequency

 
25...400 Hz
 

Minimum Switching Current [Imin]

 
5 mA for the signal circuit.
 

Insulation Resistance

 
10 MΩ for the signal circuit.

Non - overlapping Time

 
1.5 ms between NC and NO contacts when de - energized. 1.5 ms between NC and NO contacts when energized.
 

Mounting Method

 
Rail mounting Panel mounting
 

Environment

 

Standards Conformance

 
IEC 60947 - 1 IEC 60947 - 4 - 1 GB/T 14048.4
 

Product Certification

 
CE UKCA CCC
 

IP Protection Rating

 
IP2X for the front panel, applicable to the main circuit, in accordance with IEC 60529. IP2X for the front panel, applicable to the coil circuit, in accordance with IEC 60529.
 

Protective Measures

 
TH, in accordance with IEC 60068 - 2 - 30.
 

Ambient Air Temperature

 
  • 40…60 °C for operation. 60…70 °C with derating.
  • 60…80 °C for storage.
 

Working Altitude

 
3000 m without derating.
 

Fire and Abnormal High - temperature Resistance

 
850 °C, in accordance with IEC 60695 - 2 - 11.
 

Shock and Vibration Resistance

 
Vibration resistance when contacts are open (2 gn (5...300 Hz)), in accordance with IEC 60068 - 2 - 6. Vibration resistance when contacts are closed (4 gn (5...300 Hz)), in accordance with IEC 60068 - 2 - 6. Shock resistance 11 ms when contacts are open (10 gn), in accordance with IEC 60068 - 2 - 27. Shock resistance 11 ms when contacts are closed (15 gn), in accordance with IEC 60068 - 2 - 27.
 

Height

 
77 mm
 

Width

 
45 mm
 

Depth

 
86 mm
 

Net Weight

 
0.325 kg
 

Packaging Unit

 
Unit Type of Package 1: PCE Number of Units in Package 1: 1 Package 1 Height: 5.152 cm Package 1 Width: 7.874 cm Package 1 Length: 9.441 cm Package 1 Weight: 341.0 g Unit Type of Package 2: S02 Number of Units in Package 2: 24 Package 2 Height: 15.0 cm Package 2 Width: 30.0 cm Package 2 Length: 40.0 cm Package 2 Weight: 8.771 kg Unit Type of Package 3: PAL Number of Units in Package 3: 384 Package 3 Height: 60.0 cm Package 3 Width: 80.0 cm Package 3 Length: 75.0 cm Package 3 Weight: 130.994 kg
 

Contract Warranty

 
Warranty 18 months

  • Schneider LC1D12CC7C Related Video: